Curriculum
Course: AQA A Level Physics 7408
Login

Curriculum

AQA A Level Physics 7408

2. Particles and Radiation

0/58 Dr Dabour Hub Science Diagram and Course Material

3. Waves

0/39 Dr Dabour Hub Science Diagram and Course Material

4. Mechanics and Materials

0/77 Dr Dabour Hub Science Diagram and Course Material

5. Electricity

0/25 Dr Dabour Hub Science Diagram and Course Material

6. Further Mechanics and Thermal Physics

0/77 Dr Dabour Hub Science Diagram and Course Material

7. Fields and Their Consequences

0/111 Dr Dabour Hub Science Diagram and Course Material

8. Nuclear Physics

0/56 Dr Dabour Hub Science Diagram and Course Material

9. Astrophysics

0/65 Dr Dabour Hub Science Diagram and Course Material

10. Medical Physics

0/64 Dr Dabour Hub Science Diagram and Course Material

11. Engineering Physics

0/46 Dr Dabour Hub Science Diagram and Course Material

12. Turning Points in Physics

0/56 Dr Dabour Hub Science Diagram and Course Material
Text lesson

7.10.4 Transformer Efficiency

7.10.4 Transformer Efficiency — AQA A Level Physics 7408 notes: Define and calculate the efficiency of a transformer and relate it to power transmission.

Definition of efficiency · Definition of efficiency
Definition of efficiency
Real transformers are not perfect. Some of the input power is converted to thermal energy rather than delivered to the load. The efficiency is the ratio of useful output power to total input power:
efficiency = Pout / Pin = (VsIs) / (VpIp)
It is usually quoted as a percentage by multiplying by 100. It cannot exceed 100 per cent.
Definition of efficiency
Large power transformers in the grid reach 98 to 99 per cent

but small chargers may be only 80 to 90 per cent efficient.
Since energy is conserved, the missing power is not destroyed

it is dissipated as heat (and a small amount of sound and radiation) in the transformer.
1Power loss2Power loss3Power loss
Power loss
Power loss
The power lost is Ploss = Pin − Pout.
1 / 3Next ▶
Power loss
Power loss
For a transformer that is 92 per cent efficient delivering 460 W, the input is
460
⁄
0
.92 = 500 W and the loss is 40 W.
Because the losses appear as heat, a transformer with high losses becomes warm

large grid transformers are oil-cooled to carry away the heat.
◀ Previous2 / 3Next ▶
Graph of power in the load and power wasted in the source against load resistance, with the load power peaking where R equals r.
Power loss
Graph of power in the load and power wasted in the source against load resistance, with the load power peaking where R equals r." loading= - Dr Khaled Dabour Academy⤢ Enlarge
Power loss
Equivalent forms of the same relation: Pout = efficiency × Pin, and Pin = Pout/efficiency. In calculations, the turns ratio alone gives only the voltage ratio

the currents are no longer in the inverse ratio of the turns when there are lossesso you must use the power relationship.
◀ Previous3 / 3
1Efficiency in the National Grid2Efficiency in the National Grid3Efficiency in the National Grid
Efficiency in the National Grid
1

In the Grid, electricity passes through several transformers and cables between the power station and a home.
2

1
3

Transmission loss in cables is I
4

2
5

R.
6

To keep this small, the voltage is stepped up to hundreds of kilovolts, reducing the current.
1 / 3Next ▶
Efficiency in the National Grid
1

3
2

The overall efficiency of delivery is the product of the efficiencies of each stage.
3

4
4

For example, if the step-up, transmission and step-down stages have efficiencies of 0.99, 0.97 and 0.98, the overall efficiency is 0.99 × 0.97 × 0.98 = 0.94,
5

or 94 per cent.
6

A key idea is that the fraction of power lost in the cables is Ploss/P = I2R/(VI) = PR/V2

so the fractional loss falls with the square of the transmission voltage.
◀ Previous2 / 3Next ▶
Line graph of overall efficiency against the number of 80% efficient stages in sequence, falling from 80% to 32.8% over five stages
Efficiency in the National Grid
Line graph of overall efficiency against the number of 80% efficient stages in sequence, falling from 80% to 32.8% over five stages" loading= - Dr Khaled Dabour Academy⤢ Enlarge
Efficiency in the National Grid
What the symbols mean:
P = power (W) · I = current (A) · R = resistance (Ω)
◀ Previous3 / 3
Improving efficiency
1

Designers reduce losses by choosing materials and structure carefully

which is the subject of the next lesson. Efficiency also depends on loading: a transformer is usually most efficient when delivering close to its rated power, since the no-load losses (core losses that exist even when no current is drawn) are fixed while the copper losses grow with current squared.
2

When answering an exam question, show the ratio explicitly, state units, and where possible comment on whether the answer is reasonable (a value above 100 per cent signals an error).
1Additional notes2Additional notes3Additional notes
Additional notes
Additional notes
Typical values are worth remembering for comparison questions.
1 / 3Next ▶
Additional notes
Additional notes
A laptop charger might be 85 to 90 per cent efficient, a pole-mounted distribution transformer around 98 per cent,
and a very large grid transformer above 99 per cent.
In extended answers, link the cause of each loss to the improvement used: thick copper windings, a laminated core and soft iron all raise efficiency.
If asked how efficiency is found experimentally, measure the input and output voltage and current with meters (or power meters), calculate each power,
and divide,
then repeat for several loads to see how efficiency varies.
◀ Previous2 / 3Next ▶
Additional notes
1

A typical load curve rises quickly from a low value at very light load, since the fixed core losses dominate, reaches a broad maximum near the rated power

and then falls slightly at overload as the I2R heating in the windings grows. Describing this shape in words is a good way to show understanding when no data are given.
2

An ideal transformer is 100% efficient

so the power delivered by its secondary coil equals the power supplied to its primary.
3

Eddy currents flow in a solid iron core and waste energy by generating heat in it.
4

Building the iron core from thin layers of metal insulated from each other greatly reduces eddy currents.
5

A core made from a metal with high resistivity also reduces eddy currents.
6

Repeatedly reversing the magnetism of the core is a further source of energy loss.
◀ Previous3 / 3
1Worked examples2Worked examples
Worked examples
1

Worked example 1. A transformer takes 1.5 A at 230 V and delivers 11.5 V at 28 A. Calculate its efficiency.
2

Pin = 230 × 1.5 = 345 W

Pout = 11.5 × 28 = 322 W.
3

Efficiency = 322⁄345 = 0.93, or 93 per cent.
4

Worked example 2. A 96 per cent efficient transformer delivers 1.2 kW to a load. Find the input power and the power lost.
5

Pin = 1200/0.96 = 1250 W.
6

Loss = 1250 − 1200 = 50 W.
1 / 2Next ▶
Worked examples
Worked examples
Worked example 3. A transformer of efficiency 90 per cent is connected to a 240 V supply and supplies 12 V to a lamp rated 60 W. Find the primary current.
Pout = 60 W so Pin = 60⁄0.90 = 66.7 W.
Ip = 66.7/240 = 0.28 A. An ideal transformer would draw 0.25 A.
◀ Previous2 / 2
Key terms
Term Meaning
Efficiency Useful power output divided by total power input.
Power loss Input power minus output power, mostly as heat.
Copper loss I2R heating in the coil windings.
Rated power The output power the transformer is designed to supply.
National Grid The network that transmits electricity from power stations to consumers.
1Avoid these mistakes2Avoid these mistakes
Avoid these mistakes
1Avoid this
Quoting an efficiency above 100 per cent, usually from dividing input by output.Avoid this
2Avoid this
Using the turns ratio to find the secondary current without allowing for losses.Avoid this
3Avoid this
Thinking lost power disappears. It is transferred as heat to the surroundings.Avoid this
1 / 2Next ▶
Avoid these mistakes
4Avoid this
Forgetting to convert efficiency from a percentage to a fraction before multiplying.Avoid this
5Avoid this
Assuming a transformer is equally efficient at any load.Avoid this